Influences of superconducting fault current limiter (SFCL) on superconducting generator in one-machine double-line system
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY
- ,
- ,
- ,
- ,
- 巻
- 13
- 号
- 2
- 開始ページ
- 2206
- 終了ページ
- 2209
- 記述言語
- 英語
- 掲載種別
- 研究論文(学術雑誌)
- DOI
- 10.1109/TASC.2003.813037
- 出版者・発行元
- IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
Analysis of superconducting generator in single machine double-line infinite-bus transmission system equipped with SFCL's has, been performed by use of EMTDC/PSCAD. When some faults occur in one transmission line, the SFCL in the fault line operates and then the peak fault current can be limited to expected value by use of a function of the SFCL. However, in some cases, the SFCL in the other sound line has been also proved to occasionally operate due to the interaction through each transmission line. Problems, due to an installation of the SFCL's in such a model system and the influences on the superconducting generator have been pointed out by simulation analysis.