Influences of superconducting fault current limiter (SFCL) on superconducting generator in one-machine double-line system

IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY
  • Muta, I
  • ,
  • T Doshita
  • ,
  • T Nakamura
  • ,
  • T Egi
  • ,
  • T Hoshino

13
2
開始ページ
2206
終了ページ
2209
記述言語
英語
掲載種別
研究論文(学術雑誌)
DOI
10.1109/TASC.2003.813037
出版者・発行元
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC

Analysis of superconducting generator in single machine double-line infinite-bus transmission system equipped with SFCL's has, been performed by use of EMTDC/PSCAD. When some faults occur in one transmission line, the SFCL in the fault line operates and then the peak fault current can be limited to expected value by use of a function of the SFCL. However, in some cases, the SFCL in the other sound line has been also proved to occasionally operate due to the interaction through each transmission line. Problems, due to an installation of the SFCL's in such a model system and the influences on the superconducting generator have been pointed out by simulation analysis.