Proposal for control method to suppress increase in DC voltage when inverter stops during motor regeneration

IEEJ Transactions on Industry Applications
  • Jun-Ichi Itoh
  • ,
  • Tsuyoshi Nagano
  • ,
  • Wataru Aoki
  • ,
  • Akio Toba

136
2
開始ページ
90
終了ページ
99
記述言語
日本語
掲載種別
研究論文(学術雑誌)
DOI
10.1541/ieejias.136.90
出版者・発行元
Institute of Electrical Engineers of Japan

In the power conversion system of electric vehicles, the inverter is shut down when the system fails owing to a drastic load change or other protection reasons. However, when the inverter is shut down in regeneration mode, the DC link capacitor voltage increases dramatically, which will potentially destroy the switching devices. In this paper, the authors propose a halt method to overcome the overvoltage and overcurrent problems if a system failure occurs during the regeneration. In addition, the command voltage vector in Phase 1 is considered from the temporal transition of energy in the drive system in order to suppress the current amplitude. The experimental results demonstrate that the DC link capacitor voltage is 80% lower as compared with that in the conventional method.