論文

査読有り
1995年3月

非共沸混合冷媒の水平溝付管内沸騰熱伝達と圧力損失

日本冷凍協会論文集 Vol.12,No.1 pp.53~62
  • 大北 裕司

12
1
開始ページ
53
終了ページ
62
記述言語
日本語
掲載種別
DOI
10.11322/tjsrae.12.53
出版者・発行元
公益社団法人 日本冷凍空調学会

The evaporation of HCFC141b, HFC152a and HFC23, and non-azeotropic refrigerant mixture used at the very low temperature refrigeration system is experimentally studied in a horizontal spirally grooved tube with corrugation.<br>The experiments were conducted at 0.03 to 0.47MPa of boiling pressure, 100 kg/(m2s) of mass flux, 1 to 15 kW/ m2 of heat flux, -26 to 21 &deg;C of refrigerant temperature and 11.4 mm of average inner diameter.<br>It is concluded that boiling heat transfer coefficients of single-refrigerant are higher than these of non-azeotropic refrigerant mixture. And dimensionless correlation of the heat transfer coefficirnts, i.e. Lockhart-Martinelli parameters agreed with equation (10) within the limit of &plusmn;40 percent. Pressure drops of these refrigerant mixture depend on its liquid density and flow pattern.

リンク情報
DOI
https://doi.org/10.11322/tjsrae.12.53
CiNii Articles
http://ci.nii.ac.jp/naid/10002713144
CiNii Books
http://ci.nii.ac.jp/ncid/AN10035654
ID情報
  • DOI : 10.11322/tjsrae.12.53
  • ISSN : 0910-0040
  • CiNii Articles ID : 10002713144
  • CiNii Books ID : AN10035654

エクスポート