1995年3月
非共沸混合冷媒の水平溝付管内沸騰熱伝達と圧力損失
日本冷凍協会論文集 Vol.12,No.1 pp.53~62
- 巻
- 12
- 号
- 1
- 開始ページ
- 53
- 終了ページ
- 62
- 記述言語
- 日本語
- 掲載種別
- DOI
- 10.11322/tjsrae.12.53
- 出版者・発行元
- 公益社団法人 日本冷凍空調学会
The evaporation of HCFC141b, HFC152a and HFC23, and non-azeotropic refrigerant mixture used at the very low temperature refrigeration system is experimentally studied in a horizontal spirally grooved tube with corrugation.<br>The experiments were conducted at 0.03 to 0.47MPa of boiling pressure, 100 kg/(m2s) of mass flux, 1 to 15 kW/ m2 of heat flux, -26 to 21 °C of refrigerant temperature and 11.4 mm of average inner diameter.<br>It is concluded that boiling heat transfer coefficients of single-refrigerant are higher than these of non-azeotropic refrigerant mixture. And dimensionless correlation of the heat transfer coefficirnts, i.e. Lockhart-Martinelli parameters agreed with equation (10) within the limit of ±40 percent. Pressure drops of these refrigerant mixture depend on its liquid density and flow pattern.
- リンク情報
-
- DOI
- https://doi.org/10.11322/tjsrae.12.53
- CiNii Articles
- http://ci.nii.ac.jp/naid/10002713144
- CiNii Books
- http://ci.nii.ac.jp/ncid/AN10035654
- ID情報
-
- DOI : 10.11322/tjsrae.12.53
- ISSN : 0910-0040
- CiNii Articles ID : 10002713144
- CiNii Books ID : AN10035654