An Analysis of Superconducting Fault Current Limiter for Stabilization of Synchronous Generators in Multi-Machine System—Two-Machine-Infinite Bus System
The transactions of the Institute of Electrical Engineers of Japan.B
- ,
- ,
- ,
- 巻
- 123
- 号
- 2
- 開始ページ
- 133
- 終了ページ
- 142
- 記述言語
- 英語
- 掲載種別
- DOI
- 10.1541/ieejpes.123.133
This paper presents the results of analyses of the effectiveness of a superconducting fault current limiter (SFCL) to stabilize the synchronous generators, suppress turbine shaft torque oscillations, and limit the fault current in a two-machine-infinite bus system. In this study, the system model with two SFCLs having shunt resistance installed at each generator terminal was used taking 3LG (three lines to ground) fault at 12 fault points into account. These analyses were performed using EMTP/ATP, It is concluded that the use of SFCL with shunt resistance value of 1.1 pu is most effective for all fault points for the stabilization of synchronous generators, the suppression of turbine shaft torque oscillations, and the limitation of fault current. © 2003, The Institute of Electrical Engineers of Japan. All rights reserved.