A study on DC hybrid three-phase fault current limiting interrupter for a power distribution system
PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS
- ,
- ,
- ,
- ,
- ,
- ,
- 巻
- 426
- 号
- 2
- 開始ページ
- 1380
- 終了ページ
- 1384
- 記述言語
- 英語
- 掲載種別
- 研究論文(学術雑誌)
- DOI
- 10.1016/j.physc.2005.01.070
- 出版者・発行元
- ELSEVIER SCIENCE BV
For the purpose of protecting electric power system, many researches and developments of fault current limiters are being performed. The authors studied a dc hybrid three-phase fault current limiting interrupter (FCLI) composed of a superconducting reactor and an S/N transition element, connected in series each other. The dc hybrid type fault current limiting interrupter can limit a fault current by means of the inductance of high temperature superconducting (HTS) coil together with the normal transition of HTS bulk material (HTSB). In the case of an accident, the normal transition of the bulk material can be accelerated by the magnetic field of the HTS coil. In this paper, the dc hybrid type fault current limiting interrupter for 5.5 km long 6.6 kV-600 A power distribution system is analyzed, and performances of fault current limitation and interruption are confirmed. Moreover, a reclosing operation is discussed for this power distribution system. (c) 2005 Elsevier B.V. All rights reserved.