E-43 給気口の設置高さや種類別にみた侵入外気の床暖房時温熱環境に及ぼす影響

空気調和・衛生工学会大会 学術講演論文集
  • 飯野 由香利
  • ,
  • 岩本 静男
  • ,
  • 倉渕 隆
  • ,
  • 近藤 武士
  • ,
  • 遠藤 智行

2006
0
開始ページ
1185
終了ページ
1188
記述言語
日本語
掲載種別
DOI
10.18948/shasetaikai.2006.2.0_1185
出版者・発行元
公益社団法人 空気調和・衛生工学会

The experiment was conducted in order to clarify influences of outdoor air supplied through openings on thermal environment in rooms heated by floor heating systems. The ari supply openings of various heights and types were used in respective experiment cases. The following results were obtained: (1) Draught Rating (DR) was increased by sypplied outdoor air in any heights of air supply openings and openings with natural ventilation systems. The DR in areas near the air supply openings were higher than DR in far area. (2) Influences of outdoor air supplied through openings in the heights of more than 1600mm above floor were small on thermal environment. (3) The air supply openings with mechanical ventilaion systems made better thermal temperature than openings with natural ventilation systems because mechanical ventilaion systems controled temperatures of supply air.